Panel Current Source 4-20 mA
VE service typ PZP 1.1
Checking and manual control of analogue current loops 4-20mA
Operating modes
Mode A (automatic)
- current goes through the device unchanged to the receiver. Current magnitude is indicated in % by a LED bargraph.
Mode M (manual)
- input current loop is interrupted, output current can be controlled manually using “Increase” and “Decrease” buttons. Its magnitude is again indicated in % by a LED bargraph. The device can be switched back to automatic mode either by pressing M/A button or by applying a voltage signal (closing contacts) to AUT terminals.
Specifications
- Current range: 4 - 20mA
- Internal current source: 4 - 20mA (max. 25 mA)
- Display: 0-100 %, of 10 %
- Switching to AUT mode: 12-30V DC or normally open contact
- Maximum load resistance: max.240 Ω
- Internal resistance: 56 Ω
- Power supply: 230 V / 50-60 Hz
- Power consumption: max. 2VA
- Enclosure rating: IP54 (front panel), IP20 (other sides)
- Dimensions (width x height x depth): 48 x 48 x 90 (mm)
- Weight: 170 g
- Operating environment: Ambient temperature range 10 - 35 °C
- Relative humidity range: 30 až 70 %
- Storage environment (Ambient temperature range): -10 až +40 °C
- This device can optionally be supplied with galvanic isolation between input and output.